小型数据中心空调解决方案

 海洛斯精密空调    |      2016-04-06
针对小型数据中心的空调解决方案,数据中心的特点为资料处理工作场所,数据中心有大量发热设备,数据中心内人员不会太多。根据小型数据中心的特点,空调选型推荐如下:HIMOD P16机型。
This is a solution of A/C for a small data center. The characteristic of the small data center is the workplace in data processing facility, and there is a large amount of equipment. Personnel are not too much. According to the characteristics of the space for the small data center, the selection of model is recommended as HIMOD P16.
经济效益评估:(Economic Evaluation)
  • 该小型数据中心需安装空调面积总计100平方米左右,有大量发热设备(12KW),对温湿控制及节能有要求,依据实际情况每平米所需制冷量平均按350W计算,总需求47KW制冷量。
The total area is of about 100 square meters for the small data center, and there is a large amount of heat source (12KW), and it requires the temperature and humidity control and energy saving features. Required cooling capacity per square meter on average calculated based on the actual situation according to 350W, the total demand for cooling capacity is of 47KW.
  • 要满足该项目47KW的制冷量,需使用HIMOD P16机组1套装机。
To meet the cooling capacity of 47KW, this project is needed to use one set of unit (HIMOD P16).
  • 经济效益对比估算:传统空调满足47KW制冷量的输入功率至少为16KW左右,而HIMOD P16机组1套主机的输入功率合计为10.5KW,主机部分省电34.5%,全年共计节省电费1万元以上。(按1年运行8个月,1月运行30天,1天运行8小时,用电按1元1度计算)
Comparison of economic benefit estimation: the traditional air-conditioning input power (47KW cooling capacity) is at least about 16KW, and the HIMOD P16 input power per set is of 10.5KW. The energy saving is up to 34.5%. The annual saving is more than 10000 CNY. (According to 8 months per year, 30 days per month, 8 hours per day of operation, electricity by 1 CNY/1 degree calculation)